Danfoss
Danfoss 131B5235 VLT AutomationDrive FC 301 7.5kW 10HP 3-Phase 380–480V IP66 VFD
Danfoss 131B5235 VLT AutomationDrive FC 301 7.5kW 10HP 3-Phase 380–480V IP66 VFD
픽업 사용 가능 여부를 로드할 수 없습니다.
Danfoss 131B5235 VLT® AutomationDrive FC 301 7.5kW VFD
| Specification | Product Data |
|---|---|
| Brand | Danfoss |
| Part Number | 131B5235 |
| Exact Type Code | FC-301P7K5T4E66H1XGXXXXSXXXXAXBXCXXXXDX |
| Series | VLT® AutomationDrive FC 301 |
| Product Type | Variable Frequency Drive (VFD) |
| Rated Motor Power | 7.5 kW / 10 HP (HO and NO nameplate ratings) |
| High Overload Capability | Up to 160% rated output current for 60 seconds (Danfoss FC 301/302 design guide) |
| Input Phase | 3-Phase AC (Three-Phase Input) |
| Input Voltage | 3 × 380–480 VAC |
| Input Frequency | 50/60 Hz |
| Input Current — 380–440 V | 14.4 A (HO and NO; actual product nameplate) |
| Input Current — 441–480 V | 13.0 A (HO and NO; actual product nameplate) |
| Output Phase | 3-Phase AC (Three-Phase Output) |
| Output Voltage | 3 × 0–Vin |
| Output Frequency | 0–590 Hz (actual product nameplate) |
| Continuous Output Current — 380–440 V | 16.0 A (HO and NO) |
| Continuous Output Current — 441–480 V | 14.5 A (HO and NO) |
| Intermittent Output Current — 60 s | 25.6 A (380–440 V) / 23.2 A (441–480 V); Danfoss FC 301/302 design guide |
| Enclosure Protection | IP66 / UL Type 4X (E66) |
| Frame Size | A5 (actual unit and package labels) |
| RFI Filter | H1 — Class A1/B (IEC 61800-3 Category C1) |
| Brake IGBT / Chopper | X — No Brake IGBT / brake chopper |
| Local Control Panel | G — Graphical Local Control Panel LCP 102 specified by type code; physical inclusion to confirm |
| PCB Coating | X — Standard coated PCB, Class 3C2 |
| Mains Option | X — No mains option / disconnect |
| Adaptation A | X — Standard cable entries |
| Adaptation B | X — No adaptation |
| Software Release Code | SXXX — Standard software release designation |
| Software Language Pack | X — Standard language package |
| A-Option / Fieldbus Card | AX — No fieldbus option card (FC 301/302 type-code definition) |
| Software Version on Product and Packaging Labels | 09.61 — Language 1 |
| Discharge Warning on Unit | Wait 4 minutes after disconnecting mains before service |
| Country of Manufacture on Label | China |
Product Overview
The Danfoss 131B5235 is a VLT® AutomationDrive FC 301 variable frequency drive with exact type code FC-301P7K5T4E66H1XGXXXXSXXXXAXBXCXXXXDX. The supplied actual-unit and carton-label photographs show matching part number 131B5235 and serial number 010126A155. Both labels specify 7.5 kW / 10 HP in high-overload (HO) and normal-overload (NO) nameplate modes, 3-phase 380–480 VAC, 50/60 Hz input, and 3-phase 0–Vin, 0–590 Hz output. Input current is 14.4/13.0 A and output current is 16.0/14.5 A at the lower/higher voltage bands. The unit and carton labels identify IP66 / UL Type 4X and A5 frame, with 45°C / 113°F label ambient rating. The FC 301 manufacturer type-code guide identifies an H1 RFI filter (Category C1), X no brake IGBT, G graphical LCP 102 configuration, X standard coated PCB (Class 3C2), and AX no fieldbus option card. The AX code here is not the same as FC 280 AX; it does not establish an installed Modbus RTU fieldbus option. The side-view photographs do not show the control panel front, so physically included accessories must be confirmed. Please verify the exact model, final delivery schedule, applicable installation requirements, and requested accessories before ordering.
Key Product Features
- 7.5 kW / 10 HP — FC 301 P7K5 power shown on both unit and carton labels
- Three-Phase 380–480 VAC Input — 50/60 Hz mains and three-phase 0–590 Hz output
- 16.0 A / 14.5 A Continuous Output Current — lower/higher voltage-band ratings on the actual nameplate
- Up to 160% High Overload for 60 Seconds — manufacturer FC 301/302 high-overload rating
- IP66 / UL Type 4X, A5 Frame — both enclosure rating and frame identified on actual labels
- H1 RFI Filter, Category C1 — FC 301 configuration; no brake IGBT with X code
- Graphical LCP 102 (G), Standard Coated PCB (3C2), AX No Fieldbus Card — manufacturer type-code configuration; accessories subject to confirmation
Actual Product Verification
Available to Order — Estimated Delivery 3–4 Weeks
Danfoss 131B5235 is available to order with an estimated delivery time of 3–4 weeks, based on the supplied commercial information. Please reconfirm the final delivery schedule when placing the order.
Danfoss 131B5235 VLT® AutomationDrive FC 301
Contact us for project and quantity pricing. Confirm the exact model, required accessories and 3–4 week lead time.
Request Project PricingLooking for other Danfoss industrial automation products?
Explore Danfoss Industrial Automation ProductsShare