Danfoss
Danfoss 131B8877 VLT AQUA Drive FC 202 0.55kW 0.75HP 3-Phase 380–480V IP20 VFD
Danfoss 131B8877 VLT AQUA Drive FC 202 0.55kW 0.75HP 3-Phase 380–480V IP20 VFD
Tidak dapat memuat ketersediaan pengambilan
Danfoss 131B8877 VLT® AQUA Drive FC 202 0.55kW VFD
| Specification | Product Data |
|---|---|
| Brand | Danfoss |
| Part Number | 131B8877 |
| Exact Type Code | FC-202PK55T4E20H2XXXXXXSXXXXAXBXCXXXXDX |
| Series | VLT® AQUA Drive FC 202 |
| Product Type | Variable Frequency Drive (VFD) |
| Rated Motor Power | 0.55 kW (400 V) / 0.75 HP (460 V) |
| Input Phase | 3-Phase AC (Three-Phase Input) |
| Input Voltage | 3 × 380–480 VAC |
| Input Frequency | 50/60 Hz |
| Input Current (Nameplate) | 1.6/1.4 A, as printed on the supplied labels |
| Input Current at 400 V | 1.6 A continuous (Danfoss FC 202 Selection Guide) |
| Output Phase | 3-Phase AC (Three-Phase Output) |
| Output Voltage | 3 × 0–Vin |
| Output Frequency | 0–590 Hz (supplied nameplate) |
| Output Current — 380–440 V | 1.8 A continuous (Danfoss FC 202 Selection Guide) |
| Output Current — 441–480 V | 1.6 A continuous (Danfoss FC 202 Selection Guide) |
| Enclosure Protection | Open Type / IP20 / Chassis |
| Frame Size | A2 (nameplate and Danfoss FC 202 Selection Guide) |
| RFI Filter | H2 — EN 55011 Class A2 / IEC 61800-3 Category C3 |
| Brake IGBT | X — Not included |
| Local Control Panel | X — Not included (blank faceplate) |
| Mains Option | X — No mains option |
| A / Fieldbus Option | AX — No A-slot optional fieldbus card |
| B Option | BX — No B option |
| C Options | CX / X — No C option |
| D Option | DX — No D option |
| Ambient Temperature on Nameplate | 50°C / 122°F (nameplate marking) |
| Software Version on Nameplate | 05.81 — Language 1 |
| Country of Manufacture on Label | China |
Product Overview
The Danfoss 131B8877 is a VLT® AQUA Drive FC 202 variable frequency drive with exact type code FC-202PK55T4E20H2XXXXXXSXXXXAXBXCXXXXDX. The supplied unit nameplate and packaging label identify a 0.55 kW (400 V) / 0.75 HP (460 V) drive for 3-phase 380–480 VAC, 50/60 Hz input and 3-phase 0–Vin motor output. The labels show 1.6/1.4 A input current and 0–590 Hz output frequency. Danfoss FC 202 Selection Guide confirms 1.8 A continuous output at 380–440 V and 1.6 A at 441–480 V, in an Open Type / IP20, A2-frame enclosure. The H2 code indicates RFI Class A2 / Category C3; the configured X codes indicate no brake IGBT and no supplied local control panel; AX indicates no A-slot optional fieldbus card. Confirm the motor rating, available accessories and installation requirements before ordering.
Key Product Features
- 0.55 kW (400 V) / 0.75 HP (460 V) — rated motor power on the actual Danfoss nameplate
- 3 × 380–480 VAC three-phase input and 3-phase motor output
- 1.8 A / 1.6 A continuous output current for 380–440 V / 441–480 V respectively
- 0–590 Hz Output Frequency — printed on the actual unit nameplate
- IP20 / Chassis, A2 Frame — enclosure rating verified by the labels and official guide
- H2 Class A2 / C3 Filter — verified from Danfoss FC 202 type-code documentation
- No Brake IGBT / No LCP / No Optional A-Slot Fieldbus Card — exact type-code configuration
Actual Product Verification
Available to Order — Estimated Delivery 3–4 Weeks
Danfoss 131B8877 is available to order with an estimated delivery time of 3–4 weeks, based on the supplied commercial information. Please reconfirm the delivery schedule when placing the order.
Danfoss 131B8877 VLT® AQUA Drive FC 202
Contact us for project and quantity pricing. Confirm your motor rating, required accessories and lead time before ordering.
Request Project PricingLooking for other Danfoss industrial automation products?
Explore Danfoss Industrial Automation ProductsShare